OC‑F08 Fixed LPG Gas Detector Ex d IIC T6 Wall‑mount LPG Combustible Gas Transmitter 4‑20mA RS485

OC‑F08 explosion‑proof fixed LPG gas detector, 0‑100%LEL measuring range, catalytic combustion sensor. IP66 cast‑aluminum housing, 4‑20mA, RS485, relay output, compatible with PLC & DCS. For LPG stations, refineries, petrochemical plant leakage safety monitoring. Request quotation.

Get A Quote
Contact Us

OC‑F08 Fixed LPG Gas Detector

Explosion‑Proof Wall‑Mount LPG Combustible Gas Transmitter For 24/7 Industrial Leakage Monitoring

✅ Request A Quote Share your site and gas‑monitoring requirements, we reply you within 24 working hours.

Overview

The OC‑F08 fixed LPG gas detector adopts imported catalytic‑combustion sensor and ultra‑low‑power 32‑bit micro‑processor hardware platform, delivering stable, fast‑response continuous monitoring for liquefied petroleum gas(LPG) leakage in hazardous industrial zones.

This transmitter supports diffusion or optional pump‑suction sampling. Multiple industry‑standard signal outputs including 4‑20 mA analog, RS485 digital, frequency signal and relay alarm output allow seamless integration with PLC, DCS, local alarm controllers and industrial computers, realizing remote real‑time observation, over‑limit alarm and historical‑data recording.

With Ex d IIC T6 Gb flame‑proof certification and IP66 die‑cast aluminum housing, it supports long‑term unattended field‑site operation. Infrared remote‑control operation enables full parameter configuration without opening enclosure in explosive‑risk locations. Modular intelligent sensor design simplifies maintenance and sensor‑replacement work on‑site.

Besides LPG, this OC‑F08 platform supports swapping sensors to detect various combustible and toxic gases, covering ammonia, chlorine, hydrogen, formaldehyde, oxygen, hydrogen sulfide, carbon monoxide, methane, propane, carbon‑dioxide and more.

Main Applications

‑ LPG filling stations & storage yards: Real‑time LPG leakage early‑warning for tank‑area and pipeline zones.

‑ Petrochemical & Refineries: Workshop and storage‑area combustible‑gas safety supervision.

‑ Gas boiler houses & industrial kitchens: LPG leak‑detection for fuel‑consuming facilities.

‑ Chemical & Pharmaceutical Plants: Hazard‑zone flammable‑gas continuous monitoring.

‑ Mining & Coking Plants: Plant‑boundary combustible‑gas safety surveillance.

‑ Sewage‑treatment & municipal projects: Hazard‑gas monitoring for gas‑generation tank areas.

‑ Marine & On‑board installations: Cabin LPG‑risk monitoring for ship projects.

Core Advantages & Key Features

‑ Specialized LPG monitoring: Catalytic‑combustion sensor for LPG, measuring range 0‑100%LEL; diffusion sampling as standard, pump‑suction sampling optional.

‑ Rich multi‑interface output: 4‑20 mA three‑wire analog signal, RS485 Modbus digital signal, 200‑1000 Hz frequency signal; dual‑channel relay alarm output optional for linkage with exhaust fan & alarm lamp.

‑ Modular intelligent sensor: Independent air‑chamber structure; sensor auto‑identifies key parameters; no full‑unit re‑calibration after sensor replacement for easy maintenance.

‑ Infrared remote‑controller setting: Complete configuration without opening housing inside classified hazardous explosion areas.

‑ High‑anti‑interference hardware: 16‑bit ADC chip and four‑layer‑PCB circuit design, stable for complex industrial electromagnetic environment.

‑ Local LCD display: Shows gas concentration, gas type, engineering unit and instrument working‑status; ppm / %LEL / %vol / mg/m³ unit selectable.

‑ Robust explosion‑proof enclosure: Ex d IIC T6 Gb flame‑proof grade, IP66 die‑cast‑aluminum housing, fit for indoor & outdoor harsh industrial sites.

‑ Wide environmental adaptability: ‑40 ℃ ~ +70 ℃ working temp for combustible‑gas version; high‑humidity filter accessory available for damp locations.

Technical Specifications

Item OC‑F08 LPG Version Specification
Detected Gas LPG(Liquefied Petroleum Gas)
Sensor Type Catalytic combustion sensor
Measuring Range 0‑100%LEL
Resolution 1%LEL
Sampling Mode Diffusion sampling; pump‑suction circulation optional
Precision ≤ ±3 %FS
Repeatability ≤ ±2 %FS
Zero Drift ≤ ±1 %FS / year
Sensor Service Life 2‑3 years (catalytic‑combustion)
T90 Response Time ≤ 30 s
Alarm Mode Audible‑visual alarm, relay‑output alarm
Working Temperature ‑40 ℃ ~ +70 ℃ (combustible‑gas configuration)
Working Humidity 10‑95 %RH (non‑condensing); filter for high‑humidity environment optional
Working Pressure 86 kPa ~ 106 kPa
Working Voltage 24 V DC (10‑30 VDC acceptable)
Power Consumption <2.5 W (combustible‑gas)
Signal Output Standard: 4‑20 mA three‑wire signal;

Optional: RS485,200‑1000Hz frequency, two‑group relay output

Installation Wall‑mount / Pipe‑thread installation (M40*1.5)
Housing Material Die‑cast‑aluminum housing, hard‑alumina air‑chamber
Explosion‑proof Grade Ex d IIC T6 Gb
Protection Grade IP66
Electrical Thread 3/4″ NPT(Female),1/2″ NPT(Female)
Max Transmission Distance ≤ 2000 m; signal repeater for longer distance
Dimension 185 × 137.2 × 90.7 mm(L×W×H)
Weight Approx.1.6 kg
Compliance Standards GB15322.1‑2003, GB3836.1‑2010, GB3836.2‑2010, GB3836.4‑2010, GB12358‑2006
Certificates CNEx, CE, RoHS
Warranty 12‑month warranty for main unit

Remark: OC‑F08 supports sensor‑swap for many other combustible & toxic gases. Please contact sales for gas‑list, measuring‑range and alarm‑threshold confirmation.

Optional Detectable Gas Reference

Gas Detecting Range Alarm Threshold Sensor Type
NH3 0-100 PPM 25 PPM / 50 PPM Electrochemical sensor
Cl2 0-50.0 PPM 10 PPM / 20 PPM
H2 0-1000 PPM 50 PPM / 100 PPM
CH2O 0-100 PPM 25 PPM / 50 PPM
O2 0-30.0%vol 18.5%vol / 23.5%vol
H2S 0-100 PPM 10 PPM / 20 PPM
HCl 0-30.0 PPM 5.0 PPM / 10.0 PPM
HCN 0-50.0 PPM 5.0 PPM / 10.0 PPM
PH3 0-20.0 PPM 0.3 PPM / 0.6 PPM
HF 0-10.0 PPM 3.0 PPM / 6.0 PPM
NO 0-250 PPM 25 PPM / 50 PPM
CO 0-500 PPM 35 PPM / 70 PPM
SO2 0-20.0 PPM 2.0 PPM / 10.0 PPM
ClO2 0-50.0 PPM 0.3 PPM / 0.5 PPM
NO2 0-20.0 PPM 1.0 PPM / 2.0 PPM
C2H4O 0-100 PPM 10 PPM / 20 PPM
O3 0-20.0 PPM 5.0 PPM / 10.0 PPM
CH4 0-100%LEL 25%LEL / 50%LEL Catalytic combustion sensor
C3H8 0-100%LEL 25%LEL / 50%LEL
H2 0-100%LEL 25%LEL / 50%LEL
NH3 0-100%LEL 25%LEL / 50%LEL
C2H4O 0-100%LEL 25%LEL / 50%LEL
CH3CH3 0-100%LEL 25%LEL / 50%LEL
C2H4 0-100%LEL 25%LEL / 50%LEL
C4H10 0-100%LEL 25%LEL / 50%LEL
C4H8 0-100%LEL 25%LEL / 50%LEL
C7H8 0-100%LEL 25%LEL / 50%LEL
C8H10 0-100%LEL 25%LEL / 50%LEL
CH4O 0-100%LEL 25%LEL / 50%LEL
C2H6O 0-100%LEL 25%LEL / 50%LEL
C3H4O 0-100%LEL 25%LEL / 50%LEL
C2H3Cl 0-100%LEL 25%LEL / 50%LEL
C3H9N 0-100%LEL 25%LEL / 50%LEL
CH3Br 0-100%LEL 25%LEL / 50%LEL
CO2 0-5.0%vol 1.0%vol / 3.0%vol NDIR infrared sensor

 

0-5000ppm 800 PPM / 1500 PPM
CH4 0-5.0%vol

0-100%vol

1.0%vol / 3.0%vol

5%vol / 10%vol

Company Profile

We Henan Oceanus is located in Henan, a land with a long history and profound cultural heritage, has been dedicated to the research, development, production, and sales of Gas detection system and Environment equipment since its establishment. With exquisite technology and outstanding quality, we have won widespread recognition in the global marketing.

1

Manufacturing & Quality Control

Every Detail Matters. Every Product Deserves Care.

At Oceanus, quality is considered throughout the manufacturing process. From component inspection and product assembly to performance verification and final inspection, we focus on every detail to ensure our products meet the applicable quality requirements before delivery.

  • Power‑on test

Each product undergoes visual and functional checks to verify component assembly, wiring connections, display operation and basic functionality before delivery.

d74fae67ea643cea444190c537a7a469_720.jpg

  • Product Aging Test

Aging tests are conducted on applicable products to evaluate operational stability and identify potential issues during continuous operation.

5a81fef44ec129de78df74213763c098_720.jpg

  • Calibration & Performance Verification

Measuring performance is verified using appropriate reference equipment and standard gases, where applicable, to help ensure reliable measurement results.

image.png

  • Final Inspection Before Delivery

Before shipment, products are checked for appearance, accessories, packaging and order-specific requirements to ensure delivery readiness.

1793949240107651.jpg

Factory Quality Assurance

Every OC‑F08 unit completes full‑sequence factory inspection before delivery:

  1. Incoming inspection for sensors, die‑cast‑aluminum housing and circuit‑board assemblies
  2. Assembly and circuit‑continuity check
  3. Full‑function power‑on aging test
  4. Multi‑point calibration for target‑gas channel
  5. Explosion‑proof safety & appearance inspection
  6. Final outgoing FQC inspection before packing

Calibration‑test records, CNEx, CE & RoHS certification documents are available upon commercial request.

Inquiry Section

Get Custom‑made Quotation For Your Application

Please tell us target‑gas type, measuring‑range, required signal‑output type, installation‑environment and quantity. Our engineering team will give configuration suggestions and quotation for your industrial‑safety‑monitoring project.

Email: info@china-oceanus.com

Telephone: +86 0371 60998169

Mobile/Whatsapp: +86 15981942832

Mobile/Whatsapp: +86 13673683950

Scroll to Top